Discussion in 'Motors' started by johnlui, Feb 1, 2019.

  1. johnlui

    johnlui New
    Builder

    Joined:
    Jan 31, 2019
    Messages:
    2
    Likes Received:
    0
    we have snychrounous motor unbalance current and trip when start we check insulation resistance all ok winding coil resistance balance .with all 3 phase motor 4.16 kv 600A full load breaker also ok did anybody have idea why it have unbalance current..
     
  2. DarrinR

    DarrinR New
    Builder

    Joined:
    Jan 23, 2019
    Messages:
    2
    Likes Received:
    0
    How are you starting it? Across the line, softstarter, vfd? Have you megger tested the motor?
    Also have you checked the excitation voltage.
     
    #2 DarrinR, Feb 3, 2019
    Last edited: Feb 4, 2019
  3. johnlui

    johnlui New
    Builder

    Joined:
    Jan 31, 2019
    Messages:
    2
    Likes Received:
    0
    hi darrin
    across the line with 4.16kv vacum circuit today we check all the megger all ok and check the relay it showns the ground current is the one trigger the tripping coil also today we check the ground ct 50:1 ratio and it looks all ok at it trips 13A ground current
     